Illumination Levels
Extract from CIBSE: SLL Lighting Handbook 2018
| Space | Recommended maintained illuminance (lux) |
|---|---|
| Internal Corridors | 100 lux on floor with uniformity 0.4 |
| Atria |
200 lux on floor with uniformity 0.4
. Some areas may need a higher level, depending upon the use of the space |
| Lift Lobbies | 100 lux on general floor with uniformity 0.4 , 200 lux in front of lift doors |
| Internal Stairwells | 100 lux horizontal |
SmartScan Lighting Management
Significant energy savings can be achieved in areas with good levels of daylight by using daylight dimming. Presence detectors can also ensure circulation spaces are not left illuminated when not being used.
Emergency Lighting
The emergency lighting standard, BS 5266-1, recommends a minimum illumination level of 1 lux along the centreline of a corridor.