Illumination Levels

The requirements will vary depending upon the industry, but typical values are 200 - 300 lux in automated process areas, 300 - 500 lux where manual operations take place and 500 - 750 lux in inspection areas.

The CIBSE: SLL Lighting Guide 1 - Industrial Environment 2018 provides guidance for specific industries and processes, although many companies have their own engineering standards.

Application Minimum maintained mean illuminance (lux) Illuminance uniformity (minimum/average)
Process areas 300 0.60
Sorting and washing of products, milling and mixing 300 0.60
Automatic processes 200 0.40
Inspection 750 0.70